Modular Block System: Burner Management

Standard Function Blocks

SB149

• Step monitoring time

W_E

If the step monitoring time has elapsed and the output parameter

W_E

changes from 0 to 1, this alarm must be evaluated. The responsibility for
this lies solely with the user.

An application example for step monitoring time can be found in
Chapter 8.

• Time delay

D_E

There are two options for time delay:

- Time delay can be used to carry out a function for the duration of the

time delay, or

- To start a function after this time (

D_E = 1).

An application example for time delay can be found in Chapter 8.

• Active steps in a sequence

To avoid a dangerous situation occurring in a process, the user must
ensure that only one step is active in a sequence at any given time.

SB149

STEP

M

70.10

.RDY Step_1

- X - RDY

M

70.12

.COND Step_1 - X - COND

M

70.08

.Step_1

- X - STEP

B - W_BA

W - W_V

Z - W_T

B - D_BA

W - D_V

Z - D_T

NEXT - X

W_E - X

D_E - X