Modular Block System: Burner Management

Standard Function Blocks

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is fault-free
(see also Programming guidelines)

RDY:

Ready signal
RDY = 1: the step “Build up minimum air pressure” ended
correctly. The next step of the sequence is enabled.

• STEP:

signals burner stat-up for the duration of a cycle.
STEP = 1: first cycle of burner start-up
STEP = 0: no burner start-up detected
This parameter must be assigned with the operand also
assigned to the input parameter

STEP of SB149 and SB157

“Ignition attempts” for the same burner.

Function

• Monitoring the flames (pilot and main flames) from burner start-up to

operating position until burner switch-off (controlled or safety shutdown
or fault lock-out)

• Restart after a controlled shutdown

• Allows a restart once only after a controlled shutdown, which has been

triggered because of a flame failure during operation.

• Monitoring the air pressure monitor, after the time has elapsed for

building-up minimum air pressure.

• Evaluating the reset, start and stop button

• Monitoring global signals from the error, monitor and safety sequences

• Carrying out a delayed start-up after the system has started so that the

safety, error, monitor and flame monitoring sequences can supply a
positive acknowledgement signal for the global signal inputs.