Modular Block System: Burner Management

6-99

VAV3:

Main valve (valve 3)
VAV3 = 1: open main valve

REGL:

REGL = 1: control enable

RUN:

RUN = 1: result of the step carried out, main flame should be
established. This status must be monitored by SB150 “Flame
monitoring” and must be registered to SB152 “Burner: start
and operator elements” (supply

RUN from SB158 to RUN from

SB150).

FLAM:

Driving the main flame monitor
Note: for main flame monitoring, supply the output parameter
FLAM from SB159 to the input parameter MONI from SB150
FLAM = 1: Monitor main flame

Function

• Monitoring burner set up

• Driving the main valve

• Driving SB150 “Flame monitoring” for main flame monitoring

• Issuing the control enable

• Reaction to the system enable from SB152 “Burner: Start-up and

operating elements”.

Error messages

Any fault that is detected will be stored statically in the corresponding data
word (SSNR) of DB015 (1st data block).

• Error messages in DB015

- Bit 00: non-defined step is called up: safety shutdown occurs.

Remedy: only choose permitted values for the input parameter
NEXT of the current step (only one of the Bits 0 to 3 may be
set). Triggering the ENBL from SB152 resets the sequence
(SB149) automatically.