Uninterrupted blower control, Spurious, conflicting control signals – Pilz PSS SB FT, Basic license User Manual

Page 155

Advertising
background image

Modular Block System: Burner Management

6-111

Timing diagrams

Uninterrupted blower control

Spurious, conflicting control signals

An active

BLOW output can be reset via a NEXT pulse.

A step (to be defined by the user) which activates
blower overrun time can also affect SB160. The

RDY

output acts as an acknowledgement of the

NEXT pulse,

which can be polled in a SB149 of the cycle control.

A start pulse switches the blower
on. The

BLOW output remains set

until a stop signal is issued. A new
start pulse sets the output again.

The

STOP and the NEXT

signals have priority over the
STRT signal. An existing
STOP or NEXT signal
disables the switch-on pulse.