Modular Block System: Burner Management

Standard Function Blocks

Flame monitor error

Spurious signals when monitoring for “flame not established”

Flame monitor fault when monitoring for
“flame not established”.

After the

ENBL-output is reset, an enable is not set even with valid “1”-

Signals at

F_S1 and RUN.

Monitoring for “flame established” must be first run through without
error, before switching to monitoring for “flame established” can be
carried out.

Only the permitted signal
combination at

F_S1/

F_S2 can reactivate the
enable.

If there is a “1”-Signal at
the MONI input,

F_S1/

F_S2 monitoring is active
and reacts immediately
when the

ENBL output is

reset.

Spurious signals /
signal combinations
at

F_S1 and F_S2 do

have no effect on the
block’s function.

Invalid signals deactivate the enable. The enable signals processed in other
program sections (flame monitor sequence, SB 152) will, via this program
section, trigger the burner to shutdown.
The enable signal will be issued again only if the inputs are

F_S2 = 1 and

F_S1 = 0. With other signal combinations, the enable remains cancelled.