6-44

Modular Block System: Burner Management

Standard Function Blocks

Timing diagrams

No automatic start after controlled shutdown

Monitoring of end positions

When

DirC = 1 the CLOSE output sets and the, ENBL must be “1”.

O! = 1: the flap leaves the OPEN position.
After the control time the flap reaches the CLOSED position.
The acknowledgement

C! = 1 resets the CLOSE output.

The

DirC input can also be reset by the user.

OPEN-output is set when DirO = 1
ENBL must be "1".
C! = 1: the flap leaves the CLOSED position.
After the control time, the flap reaches the OPEN position.
The acknowledgment

O! = 1 resets the OPEN output.

The

DirO input can also be reset by the user.

The

ENBL signal is cancelled, if both final position acknowledgements are

present. Despite a reset and

DirO/DirC signals, no outputs are reset.

The

ENBL signal is cancelled, if O!/C! are present simultaneously.

If the

O!/C! acknowledgements are valid again, they can be reset and

with

DirO/DirC the outputs can be activated again.

SB153