Modular Block System: Burner Management

6-23

Output parameters

ENBL: Enable flag bit

ENBL = 1: the signal at the N/C contact S1 is fault-free
(refer also to Programming guidelines)

Function

Spurious signals at the monitored input (e.g. a pressure monitor) cancels
the enable after a set time.

If the N/C contact functions without fault, SB151 sets the enable

ENBL. If

interference occurs, the enable is cancelled after a set time period. Short,
fleeting interferences, for example, pressure swings after the valve has
opened will have no effect on the enable.

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).

• Error messages in DB015

- Bit 09: Suppression time has elapsed, the signal is spurious

Remedy: check contact

S1 and if AuSt = 0, press the reset

button

RSET.

- Bit 14: Reset button

RSET pressed continuously or pressed too soon.

Remedy: Release reset button and press again.

- Bit 15: Signal is fault-free, but the error which occurred was not reset

(

RSET missing)

Remedy: press the reset button

RSET.

• Error Messages on the CPU-display

- E001: Parameter errors

The

SSNR does not lie within the limits of 1 ... 200. The

incorrect

SSNR is stated in DB015/DW0000 (refer also to the

section “Administration data blocks DB015, DB016 and DB017”
in chapter 5).

- E007: Invalid time value for

T_V