Timing diagrams – Pilz PSS SB FT, Basic license User Manual

Page 135

Advertising
background image

Modular Block System: Burner Management

6-91

° Ignition transformer switched off

IGNI = 0

° Safety valve open

VAV1 = 1

° Close pilot valve

VAV2 = 0

° Pilot flame not established

RUN = 0

° Do not monitor pilot flame

FLAI = 0

Timing diagrams

Automatic ignition cycle when no parameters are set for manual ignition

The

NEXT input in the byte format controls the cycle of the ignition

process similar to that of a sequence.
The cycle will be started with a single, continuous “1” from bit 0 to bit 5.

No manual ignition set via parameters:

MANU = 0.