Spurious signals, Standard function blocks sb157 – Pilz PSS SB FT, Basic license User Manual

Page 126

Advertising
background image

6-82

Modular Block System: Burner Management

Standard Function Blocks

SB157

Spurious signals

A third attempt cannot be triggered i.e. no

RDY pulses

are created as the internal timer (M064.19=0) has
timed out.
The set

STEP and ENBL outputs from SB152 have no

effect on the

SyOK input.

SB157 is in the base state and waits for the first
ignition failure.

After the monitoring time has elapsed, no further re-ignition
is triggered. By pressing the reset button and then the
START button the sequence starts with a defined starting
step (step 1).