Modular Block System: Burner Management

6-9

Timing diagrams

Setting / resetting the step without time delay and monitoring time

When

NEXT = 1, the

following step can be
activated.

The step enabling condition
must be present at the

COND-

input once only, so that the

NEXT output is set.

If the step enabling condition is met during the
next step, then the

NEXT output from the

previous step is reset.

The step is activated by a “1”-Signal at the

RDY input. The block

waits for the step enabling condition at the

COND input.

If the conditions are present, the

NEXT output is set immediately,

and at the same time the

RDY input is reset.