Error messages, Standard function blocks, Sb156 – Pilz PSS SB FT, Basic license User Manual

Page 106

Advertising
background image

6-62

Modular Block System: Burner Management

Standard Function Blocks

Exhaust valve
VAV4

Safety valve
VAV1

Burner

chamber

Main valve
VAV3

P+

P-

Gas pressure
monitor

Air pressure
monitor

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).

• Error messages in DB015

- Bit 00: Non-defined step called up:

safety shutdown is carried out.
Remedy: Only choose permitted values for the input parameter
NEXT (only one of the bits 0 to 4 may be set), press the reset
button and then the start button

- Bit 01: Safety valve

VAV1 not seated:

safety shutdown is carried out
Remedy: Check the safety valve, press the reset button and
then the start button.

- Bit 02: Main valve

VAV3 or the exhaust valve VAV4 (if present) not

seated: safety shutdown is carried out.
Remedy: Check the main valve and/or exhaust valve, press the
reset button and then the start button.

- Bit 03: Period of time for seal monitoring is exceeded:

safety shutdown is carried out.
Remedy: Press the reset button first and then the start button.