Sb151: transient suppression, Block header, Input parameters – Pilz PSS SB FT, Basic license User Manual

Page 66: Standard function blocks

Advertising
background image

6-22

Modular Block System: Burner Management

Standard Function Blocks

SB151: Transient suppression

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further infotmation about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present

S1:

N/C contact to be monitored (check with test pulse)

BASE:

Setting the time base
BASE = M110.00 (RLO = 0): time base of 50 ms, multiplied by
T_V gives a possible range of 50 ms to 27.3 min
BASE = M110.01 (RLO = 1): time base of 100 ms, multiplied
by

T_V gives a possible time range of 100 ms to 54,6 min

T_V:

Multiplier for

BASE, to determine the length of time the enable

signal should be delayed
Permitted value range: 1 ... 32767

T:

Timer, which measures the set time

AuSt:

Automatic start (reset)
AuSt = M110.01 (RLO =1): automatic start (without reset)
AuSt = M110.00 (RLO =0): no automatic start

RSET:

Reset button (N/O)

SB151

BridgedS

B - SSNR
X - S1
X - BASE

W - T_V

Z - T

X - AuSt
X - RSET

ENBL - X

Advertising
This manual is related to the following products: