Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual

Page 129

Advertising
background image

Modular Block System: Burner Management

6-85

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is fault-free
(refer also to the Programming guidelines)

RDY:

Step sequence output
If a block step is activated, the corresponding bit is set in the
output parameter

RDY.

IGNI:

Ignition transformer
IGNI = 1: switch on ignition transformer

VAV1:

Safety valve (valve 1)
VAV1 = 1: open safety valve

VAV2:

Pilot valve (valve 2)
VAV2 = 1: open pilot valve

RUN:

RUN = 1: result of the step carried out, pilot flame should be
established. This status must be monitored by SB150 “Flame
monitoring” (supply

RUN from SB 158 to RUN from SB150).

FLAI:

Driving the pilot flame monitor
Note: supply the output parameter

FLAI from SB158 to the

input parameter

MONI from SB150 for monitoring the pilot

flame.
FLAI = 1: Pilot flame monitoring

Function

• Monitoring the ignition process

• Driving the safety and pilot valves

• Selecting means of ignition: manual or automatic

• Driving SB150 FLAME_M for pilot flame monitoring

• Reaction to the system enable of SB152 “Burner: Start and operator

elements”

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (

SSNR) of DB015 (1st data block).