Timing diagrams, Standard function blocks, Sb157 – Pilz PSS SB FT, Basic license User Manual

Page 124

Advertising
background image

6-80

Modular Block System: Burner Management

Standard Function Blocks

Timing diagrams

Counting ignition attempts where time is not exceeded

Setting input parameters

ITRY = 3: three ignition attempts

T_V = 150s: time monitoring

SB157

When

Bit0 = 1 SB157 is informed that the ignition

transformer was activated. The

STEP pulse is created

with each burner start from SB152.

2nd ignition
attempt enabled
(1st ignition set)

A positive edge at

SyOK creates a RDY pulse which jumps/loops

back in the cycle control (exists from SB149) and starts the second
ignition sequence.
The

SyOK enable is granted from SB152 after a reset and start.

The

RDY and FLAs pulses are set or reset for one program cycle

only.
For a clearer display this has been technically-enhanced and
increased. The

FLAs drop out is detected within one program cycle.

3rd ignition
attempt enabled
(1st ignition set)

2nd ignition
attempt enabled
(2nd ign. set)

3rd ignition
attempt enabled
(2nd ign. set)

When

Bit3 = 1 SB157 evaluates the flame monitoring. If the

input

FLAs detects a “0” signal, this will be interpreted as an

ignition failure and stored internally.

First ingition failure in
the 2nd set
FLAs = 0, i.e. Flame
monitor responded/
energised.

After the 3rd ignition attempt, no
RDY pulse is created.

The sequence must be started
from the beginning with the initial
step (reset + start of SB152).