Pilz PSS SB FT, Basic license User Manual

Page 73

Advertising
background image

Modular Block System: Burner Management

6-29

GUAR:

Global input of the monitor sequence
GUAR = 0: controlled shutdown when AuSt = 1, safety
shutdown when

AuSt = 0

GUAR = 1: monitor sequence is inactive: no error is present

AirP:

Air pressure monitor
AirP = 1: minimum air pressure is present
AirP = 0: air pressure is below the minimum

CHAI:

Global input of the safety sequence
CHAI = 0: safety shutdown
CHAI = 1: the safety equence is inactive: no error is present

FLAs:

Global input of the flame signals
FLAs = 0: fault lock-out
FLAs = 1: flame signlas are fault-free

FTRY:

FTRY = M110.01 (RLO =1): single attemptat a restart after a
flame error in operation (only possible if AuSt = 1)
FTRY = M110.00 (RLO =0): no option for automatic restart, a
fault lock-out occurs.

RUN:

The output parameter

RUN from SB159 “Run” must be

supplied to this parameter, so information about the operating
status of the main flame can be obtained."
RUN = 1: operating position.

• D_C:

Contains the number of cycles for the delayed enable of
SB152 after the PSS has started-up. The delayed enable is
required so that the flame monitors can reach a defined
position without a fault lock-out occurring.
Example: If the minimum scan time is 50 ms and the delayed
enable 5 s, the parameter

D_C must be assigned KB100

AuSt:

Automatic start (reset) when the PSS starts up
AuSt = M110.01 (RLO =1): automatic start (without reset) is
required after a controlled shutdown
AuSt = M110.00 (RLO =0): no automatic start required after a
controlled shutdown

RSET:

Reset button (N/O)