Modular Block System: Burner Management

6-105

The

SyOK input enables the

cycle.
A “0” signal at this input sets the
outputs to a safe state.

The individual steps are enabled with
a control byte at the

NEXT input

SyOK must remain at “1” during the
complete cycle.

The

RDY output in byte format indicates the

current status of SB159.
The individual bits from this byte must be
linked with the corresponding step block so
that a timed cycle of the outputs occurs.
The duration of the individual

RDY bits,

together with the whole cycle is determined
by the

NEXT input byte.

With Bit 2 at the

NEXT input the control

enable is set, and the power regulator
can be activated.
The control enable is cancelled by Bit 3.
The burner power is reduced to ignition
power. When this is achieved, the
burner can be switched off. The start
status is made with the reset pulse at
the

SyOK input

After the main flame has been
monitored and is established,

RUN

is set.
This time is configured by the user
in the sequence block (SB149).

The output

FLAM is set after the main

flame safety time.
If a flame is not detected by the flame
monitoring block before the main flame
safety time, then a flame fault is
signalled (

FLAM = 1).

This fault creates a fault lock-out.