Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual

Page 93

Advertising
background image

Modular Block System: Burner Management

6-49

T:

Timer which measures the time

T_V

RSET:

Reset button (N/O)

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is fault-free
(refer also to the Programming guidelines)

VAV:

Driving the valve
VAV = 0: bring the valve to its start position
VAV = 1: bring the valve to its operating position

Function

• Monitoring valve status (open/closed), the direction of a change in

position and the reaction time to a change in position

• Change in valve position after a request (start position, operating

position)

• The contact bounce time due to a change in position is one cycle.

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).

• Error messages in DB 015

- Bit 00: Status of the contact

Pos1 does not correspond with the

previous drive direction.
Remedy: Check the contact and the switch time

T_V and reset

the error in the start position (

Pos1 operated, Pos2 not

operated,

Dir2 = 0) .

- Bit 01: Status of the contact

Pos2 does not correspond with the

previous drive direction.
Remedy: Check the contact and switch time

T_V and reset the

error in the start position (

Pos1 operated, Pos2 not operated

Dir2 = 0).

- Bit 02: Switch time for a change in position has been exceeded

Remedy: Check the switch time

T_V for the contact(s) and the

reset the error in the start position (

Pos1 operated, Pos2 not

operated,

Dir2 = 0).