Modular Block System: Burner Management

Standard Function Blocks

SB149

W_V:

Time value (watchdog value) of step monitoring time as
multiplier for

W_BA

Permitted value range: - 32768 ... 32767
For W_V

0 to be valid: there is no step monitoring time,

the output parameter W_E is permanently 0.

• W_T:

Timer (watchdog timer) for step monitoring time

• D_BA:

Time base for step time delay
Following values are valid:
0: 50 ms
1: 100 ms
2: 1 s
3: 10 s
4: 1 min

D_V:

Time value of the time delay as multiplier for

D_BA

Permitted vallue range: -32768 ... 32767
For

D_BA

0 to be valid: there is no time delay,

the output parameter

D_E changes immediately from 0 to 1 as

soon as a step is activated.

D_T:

Timer for time delay

Output parameters

NEXT:

Gives the status of the step
NEXT = 1: step is active

W_E:

Output parameter for step monitoring time
W_E = 1: timer for the step monitoring time has elapsed.

D_E:

Output parameter for the time delay
D_E = 1: timer for the time delay has elapsed.

Function:

• Control of work cycles

• By adding together several SB149 blocks, a step sequence can be

established

• One PSS can control and monitor several work cycles (e.g. burner), in

which each cycle is allocated a separate sequence