Modular Block System: Burner Management

Standard Function Blocks

SB154: Control and position monitoring of valves

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input Parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present

Pos1:

Limit switch (N/O contact “start position reached?”)
Pos1 = 1: valve in the “start position”
Pos1 = 0: valve not in the “start position”

Pos2:

Limit switch (N/O contact “operating position reached?”)
Pos2 = 1: valve in “operating position”
Pos2 = 0: valve not in the “operating position”

Dir1:

Drive direction
positive edge from

Dir1: valve will take up the start position

Dir2:

Drive direction
positive edge from

Dir2: valve will take up the operating

position

T_V:

Switch time for a change in position
Permitted value range: 1 ... 32767,
multiplying the value with the fixed time base of 50 ms gives a
time range from 50 ms ... 27.3 min.

SB154

VALVE

B - SSNR
X - Pos1
X - Pos2
X - Dir1
X - Dir2

W - T_V

Z - T

X - RSET

ENBL - X

VAV - X