Driving the air flaps, Examples – Pilz PSS SB FT, Basic license User Manual

Page 178

Advertising
background image

8-14

Examples

Modular Block System: Burner Management

Step [n+1]

Driving the air flaps

During the burner cycle the air dampers can be driven using SB153. After
the control enable, position monitoring is no longer required and the
motors for the dampers can be driven directly via SB153.

If you wish to carry out such programming, you can use the block diagram
as shown on the next page.

LN

M

74.00

ENBL SB152

U

M

73.01

Auxiliary flag negative edge

=

M

73.02

Pulse flag

R

M

73.01

Auxiliary flag negative edge

L

M

74.00

ENBL SB152

S

M

73.01

Auxiliary flag negative edge

L

...

Input “Open flap”

=

...

Output “OPEN: Drive flap motor”

L

...

Input “Close flap"

=

...

Output “CLOS: Drive flap motor”

1

2

SB149

STEP

M

70.00

.Step.[n,n+1]

- X - RDY

M

80.00

.COND[n+1]

- X - COND

X - STEP
B - W_BA

W - W_V

Z - W_T

B - D_BA

W - D_V

Z - D_T

NEXT - X - M

70.01

.Step.[n+1,n+2]

W_E - X

D_E - X