Timing diagrams – Pilz PSS SB FT, Basic license User Manual

Page 111

Advertising
background image

Modular Block System: Burner Management

6-67

° Open safety valve

VAV1 = 1

° Main valve closed

VAV3 = 0

° Exhaust valve closed

VAV4 = 0

° Test output

GP- = 0

° Test output

GP+ = 0

-

NEXT, Bit 03 = 1: Testing for gas pressure

° Enable

ENBL = 1

° Seal check step 4 is active

RDY, Bit 03 = 1

° Safety valve closed

VAV1 = 0

° Main valve closed

VAV3 = 0

° Exhaust valve closed

VAV4 = 0

° Test output

GP- = 0

° Test output

GP+ = 1

-

NEXT, Bit 04 = 1: Seal check ended

° Enable

ENBL = 1

° Seal check step 5 is active

RDY, Bit 04 = 1

° Safety valve closed

VAV1 = 0

° Main valve closed

VAV3 = 0

° Exhaust valve closed

VAV4 = 0

° Test output

GP- = 0

° Test output

GP+ = 0

Timing diagrams

Signal cycle of uninterrupted tightness control on a plant with an exhaust valve

The

NEXT input in the byte-format controls the SB cycle similar to that of a

step sequence.
The cycle is started with a single, continuous “1” from bit 0 to bit 4.