Pilz PSS SB FT, Basic license User Manual

Page 81

Advertising
background image

Modular Block System: Burner Management

6-37

Restart after flame failure or flame monitoring fault

When

AuSt = 1 and FTRY = 1 SB152 can begin an automatic restart once

only after flame failure or flame monitor interference. Burner start-up will
only be initiated if the safety sequence and the monitor sequence have not
responded, no interference is present and the flame and the flame
monitoring block does not signal a fault.

After air pressure has been built-up,
monitoring is activated by a pulse at the
NEXT input. The RDY output signals this
activation.
The

RDY output is used as the step

enabling condition for the sequence.

The

ENBL output is set by

a start pulse, provided all
criteria are met (

ERR,

GUAR, CHAI, FLAs)

When

RUN = 1,

“Burner in operation” is
signalled.

Flame failure of flame
monitor interference.
The

ENBL is reset

After the interference is
removed (

FLAs = 1), the

ENBL output is set again.

By a new, second
flame failure or flame
monitor fault, the
ENBL output is not set
again. Only after a
reset and a start pulse
is the

ENBL set again.