Blocks required, Standard function blocks, Sb152 – Pilz PSS SB FT, Basic license User Manual

Page 76

Advertising
background image

6-32

Modular Block System: Burner Management

Standard Function Blocks

then press the start button (

STRT).

- Bit 08: Reset via

RSET is missing

Remedy: Press the reset button (

RSET)

- Bit 09: Start button pressed (

STRT), but STOP has a constant

value 1
Remedy: Check the stop button (

STOP)

- Bit 10: Stop button pressed (

STOP), but STRT has a constant value 1

Remedy: Check start button

STRT.

- Bit 11: Pressign start (

STRT) button is missing

Remedy: Press the start button (

STRT)

- Bit 12: Time delay for the plant enable after the PSS has started is

running
Remedy: Let the time delay run and following that, press the
start button (

STRT).

- Bit 13: An error is present. Evaluation of the reset or start button

occurs only if the burner is no longer operating.

Remedy: Input parameter

RUN must be 0, i.e. SB159 must

reset this parameter if shutdown occurs.

• Error messages on the CPU-display

E001:

Parameter errors
The

SSNR does not lie within the limits 1 ... 200. The incorrect

SSNR is stated in the D015/DW0000 (see the section

“Administration data blocks DB015, DB016 and DB017” in
chapter 5).

Blocks required

• DB002:

Will be made available when the configurator is called up

• DB015:

Administration data block
DB015 must consist of its total length of 1024 words and have
Read/Write status (see also the section “Administration data
blocks DB015, DB016 and DB017” in chapter 5).

• OB101:

To call up SB152.

• SB152:

BR_START

• SB255:

To call up the operating system

SB152