6-90

Modular Block System: Burner Management

Standard Function Blocks

-

NEXT, Bit 2 = 1:

Open pilot valve

° Enable

ENBL = 1

° Ignition step 3 is active

RDY, Bit 2 = 1

° Ignition transformer switched on

IGNI = 1

° Safety valve open

VAV1 = 1

° Open pilot valve

VAV2 = 1

° Pilot flame not established

RUN = 0

° Do not monitor pilot flame

FLAI = 0

-

NEXT, Bit 3 = 1:

Pilot flame established

° Enable

ENBL = 1

° Ignition step 4 is active

RDY, Bit 3 = 1

° Ignition transformer switched on

IGNI = 1

° Safety valve open

VAV1 = 1

° Pilot valve open

VAV2 = 1

° Pilot flame established

RUN = 1

° Monitor pilot flame

FLAI = 1

-

NEXT, Bit 4 = 1:

Switch off pilot transformer

° Enable

ENBL = 1

° Ignition step 5 is active

RDY, Bit 4 = 1

° Switch off ignition transformer

IGNI = 0

° Safety valve open

VAV1 = 1

° Pilot valve open

VAV2 = 1

° Pilot flame established

RUN = 1

° Monitor pilot flame

FLAI = 1

-

NEXT, Bit 5 = 1:

Close pilot valve

° Enable

ENBL = 1

° Ignition step 6 is active

RDY, Bit 5 = 1