Sb153: control and position monitoring of flaps, Block header, Input parameters – Pilz PSS SB FT, Basic license User Manual

Page 84: Standard function blocks

Advertising
background image

6-40

Modular Block System: Burner Management

Standard Function Blocks

SB153: Control and position monitoring of flaps

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error is present

C!:

Limit switch (N/O contact “flap closed”)
C! = 1: the flap is closed and operated via the limit switch
C! = 0: limit switch not operated

O!:

Limit switch (N/O contact “flap open”)
O! = 1: the flap is opened and operated via the limit switch
O! = 0: limit switch not operated

DirO:

Drive direction
positive edge from

DirO: flap should be opened (output OPEN

= 1, until the limit switch

O! is achieved)

DirC:

Drive direction
positive edge from

DirC: flap should be closed (output CLOS

= 1)

T_V:

Switch time for the position change,
Permitted value range: 1 ... 32767,
multiplying the value with the fixed time base of
50 ms gives a time range from 50 ms ... 27.3 min.

SB153

FLAP

B - SSNR
X - C!
X - O!
X - DirO
X - DirC

W - T_V

Z - T

X - RSET

ENBL - X

OPEN - X

CLOS - X