Modular Block System: Burner Management

Standard Function Blocks

SB152: Burner: start and operator elements

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error detected.

NEXT:

NEXT = 1: Time for the step “Build-up minimum air pressure”
has elapsed, air pressure monitoring is activated (air pressure
monitor

AirP) .

STRT:

Start input to switch on the burner

STOP:

Stop input to switch off the burner

ERR:

Global input of the error sequence
ERR = 0: controlled shutdown when AuSt = 1,

safety shutdown when

AuSt = 0

ERR = 1: the error sequence is inactive, which means no error
is present.

SB152

SB152

BR_START

B - SSNR
X - NEXT
X - STRT
X - STOP
X - ERR
X - GUAR
X - AirP
X - CHAI
X - FLAs
X - FTRY
X - RUN
B - D_C
X - AuSt
X - RSET

ENBL - X

RDY - X

STEP - X