Standard function blocks, Sb158 – Pilz PSS SB FT, Basic license User Manual

Page 132

Advertising
background image

6-88

Modular Block System: Burner Management

Standard Function Blocks

L

M90.02

. VAV1 SB156

O

M90.03

. VAV1 SB158

=

A2.00

. Safety valve

Shutdown

If

SyOK = 0 or if an error is present (see error messages), a shutdown

occurs:

° No enable

ENBL = 0

° Ignition step not active

RDY = 0

° Switch off ignition transformer

IGNI = 0

° Close safety valve

VAV1 = 0

° Close pilot valve

VAV2 = 0

SB158

SB156

TIGHT_C

B - SSNR
B - NEXT
X - SyOK
X - V4?
X - P+
X - P-

W - T_V

Z - T

ENBL - X

RDY - B

VAV1 - X - M

90.02

.safety valve SB156

VAV3 - X
VAV4 - X

GP+ - X

GP- - X

SB158

IGNITION

B - SSNR
B - NEXT
X - SyOK
X - MANU
X - S_IG

ENBL - X

RDY - B

IGNI - X

VAV1 - X - M

90.03

.safety valve SB158

VAV2 - X

RUN - X

FLAI - X

Example: