6-34

Modular Block System: Burner Management

Standard Function Blocks

Timing diagrams

Burner start-up without automatic start after a controlled shutdown

Failure of safety sequence, flame monitor sequence and general faults

Failure of one of the followign criteria

• Safety sequence

CHAI = 0,

• Flame monitor sequence

FLAs = 0,

• Error sequence

ERR = 0

The

ENBL output is set with a start pulse,

provided all criteria are fulfilled (

ERR,

GUAR, CHAI, FLAs).
With each burner start-up, a pulse at the
STEP output is created, with which all
SB149 blocks and SB 157 are reset.

Failure of air pressure during
burner operation (

RUN =1 ):

ENBL is reset.

Only after a reset signal can the

ENBL-output

be set again via a start pulse. No automatic
restart is enabled.

With a pulse at

NEXT,

air pressure monitoring
is activated

If the monitor sequence is energised
(

GUAR = 0), the behaviour is identical

to that of air pressure monitoring.