Reset spurious acknowledgements, Spurious acknowledgement as valve opens – Pilz PSS SB FT, Basic license User Manual

Page 97

Advertising
background image

Modular Block System: Burner Management

6-53

Reset spurious acknowledgements

Spurious acknowledgement as valve opens

After a fault lock-out due to an incorrect acknowledgement,
a reset can only occur (with a positive edge at

RSET), if the

valve is closed (

Pos1 =1).

The valve positions OPEN/CLOSE are polled to the feedback
inputs

Pos1 and Pos2.

The inputs are polled for validity and the control time
OPEN

CLOSE and CLOSE

OPEN is monitored. If

faults occur, the

VAV output, together with the valve are

closed immediately and additionally

ENBL = 0 is set.

If the “1”-Signal remains off for a time shorter than the
block's set time, the

ENBLoutput is not set to "0".

Only after a “1” signal is off for a longer period will the
ENBL output be reset.