Modular Block System: Burner Management

SB 155: Pre-purge

Version

Date

CRC

1.0

21.07.97

902C

1.1

05.05.98

3D0B

Changes from Version 1.0 to Version 1.1

Block-internal flags are reset so that output parameters

ENBL and RDY are

not influenced for the whole duration of an existing error.

SB156: Tightness control

Version

Date

CRC

1.0

20.08.97

90EE

1.1

02.03.99

D4FF

Changes from Version 1.0 to Version 1.1
• The status of

GP+ and GP- are stored internally.

• In both steps "Test for air pressure" and "Test for gas pressure", the

pressure monitors

P+ and P- will be tested for feasibility.

SB 157: Several ignition attempts

Version

Date

CRC

1.0

12.12.97

13CB

1.1

19.03.98

9B7C

STOP

Changes from Version 1.0 to Version 1.1

• Addition of the input parameter

STEP.

- This parameter signals burner start-up for the duration of a cycle.

- The input parameter

STEP replaces the internally used Bit 0 from

DW 1021 in DB 015.

- This allows you to operate several work cycles (e.g. burners) on one

PSS.