Blocks required, Programming guidelines, Standard function blocks – Pilz PSS SB FT, Basic license User Manual

Page 68: Sb151

Advertising
background image

6-24

Modular Block System: Burner Management

Standard Function Blocks

Blocks required

• DB002:

Will be made available when the configurator is called up.

• DB015:

Administration data block
DB015 must consist of its total length of 1024 data words and
have Read/Write status (refer also to the section “Administrati-
on data blocks DB015, DB016 and DB017” in chapter 5).

• OB101:

To call up SB 151

• SB151:

BridgedS

• SB152:

BR_START for the error reaction

• SB255:

To call up the operating system

Programming guidelines

ENBL

The enable

ENBL from SB151 must be supplied to the AND-operation

before the global input

ERR or to the AND-operation before the global

input

CHAI of SB152 “Burner: Start and operator elements”. The decision

to use

ERR or CHAI depends on the user and the respective standards

regarding error reactions.

ERR:

If an error occurs, a controlled shutdown is carried out when
AuSt = 1 with restart.

CHAI: If an error occurs, a safety shutdown is carried out.

A programming example can be found in Chapter 8 under “Managing
enables”.

SB151