Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual

Page 85

Advertising
background image

Modular Block System: Burner Management

6-41

T:

Timer which measures the time

T_V

RSET:

reset button (N/O)

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is fault-free

OPEN:

OPEN = 1: open flap
OPEN = 0: no drive direction “open”

CLOS:

CLOS = 1: close flap
CLOS = 0: no drive direction “close”

Function

• Monitoring the flap status (open/closed), the direction of the change in

position and the reaction time due to a change in position

• Opening and closing a flap after a received request

• The contact-bounce time due to a change in position is one cycle.

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).

• Error messages in DB015

- Bit 00: Status of contact

C! does not correspond to the previous drive

direction.
Remedy: Check the limit switch and the switch time

T_V and

reset the error. If neither limit switch is operated, the drive
direction must be re-selected.

- Bit 01: Status of contact

O! does not correspond with the previous

drive direction.
Remedy: Check the limit switch and switch time

T_V and reset

the error. If neither limit switch is operated, the drive direction
must be re-selected.