Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual

Page 119

Advertising
background image

Modular Block System: Burner Management

6-75

STEP:

Signals burner start-up for the duration of one cycle
STEP = 1: first cycle of burner start-up
STEP = 0: no burner start-up detected
This parameter must be assigned with the operand also used
for the input parameter

STEP from SB149 and the output

parameter

STEP of SB152 “Burner: start and operator

elements” for the same burner.

T_V:

Permitted time span between the first failed attempt and the
flame being detected and established.
Permitted value range: - 32768 ... 32767
Time base: 50 ms

T:

Connection for the timer [T64 ... T127] for measuring

T_V

Output parameters

RDY:

Ready signal
Pulse signal to start the step sequence from the initial ignition

step.

Function

• Number of ignition attempts

• During a new burner start-up, after an ignition failure, a signal is issued

for a permitted re-ignition attempt, after which the step sequence can
start the initial ignition step immediately.

• Time monitoring for the ignition attempts until the flame is detected

Error messages

Error messages on the CPU-display
• E001:

Parameter errors
The

SSNR does not lie within the limits 1 ... 200. The incorrect

SSNR is stated in DB015/DW0000 (see section
“Administration data blocks DB015, DB016 and DB017” in
chapter 5).

• E007:

Invalid time value for T_V.