Modular Block System: Burner Management

6-43

• SB152:

BR_START for error reaction

• SB153:

FLAP

• SB255:

To call up the operating system

Programming guidelines

ENBL

The

ENBL of SB153 must be supplied to the AND-operation before the

global input

ERR or to the AND-operation before the global input CHAI of

SB152 “Burner: Start and operator elements”. The decision to use

ERR

or

CHAI depends on the user and the respective standards regarding

error reaction.

ERR:

If an error is present, a controlled shutdown occurs when

AuSt = 1 with restart

CHAI:

If an error is present a safety shutdown occurs

A programming example can be found in Chapter 8 under “Managing
enables.

• Driving the air dampers

During burner start-up the air dampers must be driven by SB153. After a
control enable, position monitoring is no longer required and the air
damper motors can be drive directly without SB153.
A programming example can be found in the section “driving the Air
Dampers” in Chapter 8.

DirO and DirC

Driving one flap: the drive must be driven in one direction only i.e.

DirO

and

DirC must not be driven simultaneously.