Modular Block System: Burner Management

Standard Function Blocks

SB149

With spurious signals:

If a step enabling condition is met at the

COND input, it will not

cause the outputs to set too early.

Only if the step block was activated with

RDY = 1 do the

outputs react to the step enabling condition.

Repeated “1”-Signals at the

COND input do

not cause malfunctions further on in the
process.

The

RDY output may not be set a second time after the step

block has been run through once.

Therefore, in the FS program it must be monitored that only one
individual

NEXT output is active and all other NEXT outputs

have a “0”-Signal. Should it be detected that more than one
NEXT output has a “1”-Signal, an immediate fault lockout