Blocks required, Standard function blocks, Sb150 – Pilz PSS SB FT, Basic license User Manual

Page 60

Advertising
background image

6-16

Modular Block System: Burner Management

Standard Function Blocks

- Bit07: Flame established but does not correspond to the expected

status
Remedy: Exit operating position (

RUN = 0) and bring the SB150

to the start position (

MONI = 1, F_S1 = 0, F_S2 = 1, RUN = 0).

- Bit08: Flame monitoring switched off

Remedy: Switch on flame monitoring (

MONI = 1) and bring

SB150 to the start position (

MONI = 1, F_S1 = 0, F_S2 = 1,

RUN = 0).

• Error messagess on the CPU-display

E001:

Parameter errors
The

SSNR does not lie within the limits 1 ... 200. The incorrect

SSNR is stated in DB015/DW0000 (see the section
“Administration data blocks DB015, DB016 and DB017” in
chapter 5).

Blocks required

• DB002:

Will be made available when the configurator is called up.

• DB015:

Administration data block
DB015 must consist of its total length of 1024 words and have
Read/Write status (refer also to the section “Administration data
blocks DB015, DB016 and DB017" in chapter 5).

• OB101:

To call up SB(s)150 directly in OB101 or, for example, together
in an FB.

• SB150:

FLAME_M

• SB152:

BR_START for evaluating the flame monitor global signal
FLAs.

• SB157:

IGNI_TRY for evaluating the flame monitor global signal

FLAs

when carring out several ignition attempts.