Sb156: tightness control, Block header, Input parameters – Pilz PSS SB FT, Basic license User Manual

Page 104: Standard function blocks

Advertising
background image

6-60

Modular Block System: Burner Management

Standard Function Blocks

SB156: Tightness control

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: byte constants KB001 ... KB200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB 015 = 0: no error present

NEXT:

Sequence input
Bits 0...4 of the input byte represent a processing step within
the block. By setting the bit, the corresponding step in the
block is started.

SyOK:

General plant status
Note: supply the output parameter

ENBL from SB152 to the

input parameter

SyOK of SB56

SyOK = 1: no error
SyOK = 0: error in the system, leads to shutdown

V4?:

Selection of the exhaust valve
V4? = M110.01 (RLO=1): exhaust valve VAV4 present
V4? = M110.00 (RLO=0): No separate exhaust valve present,
exhaust carried out via the main valve

VAV3

(Note: exhaust via the main valve is only permitted, if fuel
cannot come into contact with any parts in the burner chamber
whose temperature lies above the ignition temperature of the
fuel used).

SB156

TIGHT_C

B - SSNR
B - NEXT
X - SyOK
X - V4?
X - P+
X - P-

W - T_V

Z - T

ENBL - X

RDY - B

VAV1 - X
VAV3 - X
VAV4 - X

GP+ - X

GP- - X

Advertising
This manual is related to the following products: