Pilz PSS SB FT, Basic license User Manual

Page 133

Advertising
background image

Modular Block System: Burner Management

6-89

° Pilot flame not established

RUN = 0

° Monitor pilot flame

FLAI = 1

• Ignition sequence

-

NEXT = 0: Ignition not yet activated

° Enable

ENBL = 1

° Ignition step not active

RDY = 0

° Ignition transformer switched off

IGNI = 0

° Safety valve closed

VAV1 = 0

° Pilot valve closed

VAV2 = 0

° Pilot flame not established

RUN = 0

° Monitor pilot flame

FLAI = 1

-

NEXT, Bit 0 = 1: Switch on ignition transformer

° Enable

ENBL = 1

° Ignition step 1 is active

RDY, Bit 0 = 1

° Switch on ignition transformer

IGNI = 1

° Safety valve closed

VAV1 = 0

° Pilot valve closed

VAV2 = 0

° Pilot flame not established

RUN = 0

° Monitor pilot flame

FLAI = 1

-

NEXT, Bit 1 = 1:

Open safety valve

° Enable

ENBL = 1

° Ignition step 2 is active

RDY, Bit 1 = 1

° Ignition transformer switched on

IGNI = 1

° Open safety valve

VAV1 = 1

° Pilot valve closed

VAV2 = 0

° Pilot flame not established

RUN = 0

° Do not monitor pilot flame

FLAI = 0