Multiple drive commands, Spurious fault signal reset, Standard function blocks – Pilz PSS SB FT, Basic license User Manual

Page 90: Sb153

Advertising
background image

6-46

Modular Block System: Burner Management

Standard Function Blocks

Multiple drive commands

Spurious fault signal reset

Repeated drive commands,
although the final position has
already been reached.

No drive commands with invalid input
signals (both inputs “1”)
ENBL output is reset.

The outputs will be active again only after an
enable reset and a new control command edge.

After a fault signal (

ENBL = 0) the corresponding

OPEN/CLOSE output is set when there is a 0-1 edge
at the

DirO/DirC input and RSET pulse.

SB153