Sb158: ignition, Block header, Input parameters – Pilz PSS SB FT, Basic license User Manual

Page 128: Standard function blocks

Advertising
background image

6-84

Modular Block System: Burner Management

Standard Function Blocks

SB158: Ignition

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB001 ... KB200
(further information about the SSNR can be found in the
section “Administration data blocks DB015, DB016 and
DB017” and in the section “Input parameter

SSNR” in

chapter 5).
Value of DW0000/DB015 = 0: no error present

NEXT:

Step sequence input
Bits 0...5 of the input byte represents a processing step in the
block. By setting a bit the corresponding step in the block wil
be started.

SyOK:

General plant status
Note: suplpy the output parameter

ENBL of SB152 to the input

parameter

SyOK of SB158

SyOK = 1: no error
SyOK = 0: error in the system, leads to a shutdown

MANU:

MANU = M110.01 (RLO=1): manual ignition via the S_IG
button
MANU = M110.00 (RLO=0): automatic ignition via the step
sequence

S_IG:

Ignition button

SB158

IGNITION

B - SSNR
B - NEXT
X - SyOK
X - MANU
X - S_IG

ENBL - X

RDY - B

IGNI - X

VAV1 - X
VAV2 - X

RUN - X

FLAI - X