Modular Block System: Burner Management

6-93

Automatic ignition cycle when parameters are set for manual ignition

Manual ignition set via parameters:

MANU = 1.

The enable (

ENBL) is immediately

reset if there is a loss of the

SyO

signal and flame monitoring is
activated.
The safety gas valve is closed.

The ignition cycle can be started by
pressing a button. A pulse to the

S_IG

input with a simultaneous "1" of Bit 0
from the

NEXT input sets the Bit 0 of

RDY. The ignition transformer is
switched on.