Super Systems 20Q User Manual

Page 102

Advertising
background image

98

Gr. dfGr. dfGr. dfGr. dfGr. df

NOTES

NOTES

NOTES

NOTES

NOTES:
1) The fault conditions on the auxiliary input will be displayed

only if the relative indication has been selected (see "Display
function" at page. 62).

2) When a fault condition different from overrange or underrange

is detected on the auxiliary input, the alarms,the power
output and the analog retransmissions operate as in presence
of an underrange condition.

ERROR MESSAGES

ERROR MESSAGES

ERROR MESSAGES

ERROR MESSAGES

ERROR MESSAGES

At the end of each configuration parameter group modifiction the
instrument check the new parameters values.
At instrument start up in operative mode, all the parameters are
checked.

If an error is detected, the instrument will show:
- on the upper display,

the parameter family
CnF.x

for configuration parameters

GRP. x for run time parameters
CAL

for calibration parameters

where x is the number of the specific group where the
error has been detected.

- on the middle display, the "Err" indication
- on the lower display,

- for configuration or run time parameter, it will show

the mnemonic code of the group with the wrong
parameter setting.

- for calibration parameter, it will show the mnemonic

code of the wrong calibration parameter.

The device resets automatically after a time out of 6 s (20 s if
serial link is enabled)

Configuration and run time parameter errors.

Configuration and run time parameter errors.

Configuration and run time parameter errors.

Configuration and run time parameter errors.

Configuration and run time parameter errors.
When one of this error is detected, following the procedures
described for standard parameter modification reach the group
with the wrong parameter setting and correct it (every keystroke
restarts the time out. The time out is disabled when modify
configuration parameters mode is enabled)
When the error is corrected push “MENU” until the device resets
(if in run mode) or end the modify configuration parameters mode
following the normal procedure.
Repeat the above described procedure if another error is shown.