CnF. EndCnF. EndCnF. EndCnF. EndCnF. End

59

- Out failure detection (OFD) - [C.I11]

- Out failure detection (OFD) - [C.I11]

- Out failure detection (OFD) - [C.I11]

- Out failure detection (OFD) - [C.I11]

- Out failure detection (OFD) - [C.I11]

This parameter will be available only when the option is fitted
and the main and/or the secondary output is configured as time
proportional control output
Range: nonE = Function not provided

ñC.On = Set “Fd.Fn” to “ñC.On” when the load under

test is energized during the ON status of the
main output (relay energized or SSR output
status 1).

ñC.OF = Set “Fd.Fn” to “ñC.OF” when the load under

test is energized during the OFF status of the
main output (relay de-energized or SSR output
status 0).

SC.On = Set “Fd.Fn” to “SC.On” when the load under test

is energized during the ON status of the secondary
output (relay energized or SSR output status 1).

SC.OF= Set “Fd.Fn” to “SC.OF” when the load under test

is energized during the OFF status of the secondary
output (relay de-energized or SSR output status 0).

NOTE

NOTE

NOTE

NOTE

NOTE: When the option is not fitted the middle display will show
“no.Pr”

- Primary current of the current trans-

- Primary current of the current trans-

- Primary current of the current trans-

- Primary current of the current trans-

- Primary current of the current trans-

former

former

former

former

former

- [C.I12]

- [C.I12]

- [C.I12]

- [C.I12]

- [C.I12]

This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: From 10 A to 100 A

- Out failure detection - output

- Out failure detection - output

- Out failure detection - output

- Out failure detection - output

- Out failure detection - output

assignment

assignment

assignment

assignment

assignment - [C.I13]

- [C.I13]

- [C.I13]

- [C.I13]

- [C.I13]

This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: nonE = The "Out failure detection" alarm is signalled

only on display

OUt.1 = The "Out failure detection" alarm is signalled on

OUT 1

OUt.2 = The "Out failure detection" alarm is signalled on

OUT 2

OUt.3 = The "Out failure detection" alarm is signalled on

OUT 3

OUt.4 = The "Out failure detection" alarm is signalled on

OUT 4

NOTE

NOTE

NOTE

NOTE

NOTE: "Out failure detection "alarm annunciator cannot be
assigned to an output just configured as control output.

CnF.6CnF.6CnF.6CnF.6CnF.6