Super Systems 20Q User Manual

Page 45

Advertising
background image

CnF. 2CnF. 2CnF. 2CnF. 2CnF. 2

41

General notes on configuration group 2

General notes on configuration group 2

General notes on configuration group 2

General notes on configuration group 2

General notes on configuration group 2
I) Exiting from the configuration group 2 the instrument verifies

automatically the congruence of all parameters. If a wrong
setting is detected, the device will show:

The group 2 parameter passes the congruence test when:
1) Only one of the 6 outputs is configured as main output

(“ñAin”)

2) Only one of the 6 outputs is configured as secondary

output (“SECn”)

3) If only one control output is configured, it should be the

main control output (“ñAin”)

4) The servomotor must be “close loop” type if it is one of two

control outputs.

NOTE

NOTE

NOTE

NOTE

NOTE: The instrument may be used as an indicator, so that this
test is satisfied even if no output is configured as control output

II) Exiting from the configuration group 2 also the following

actions are automatically performed:
A) The "Añ.UL” parameter ("Output value for auto to manual

transfer" [C.G04]) will be forced to "bumpless" (“buñ”) if:
1) its value is < 0 and only one control output is configured;
2) servomotor open loop without feedback is configured.

B) The parameter “SF.Cn” ("Condition for output safety value"

[C.G07]) will be forced to "standard" (“Std.”) if it is not complied
with configured control output type

C) The parameter “SF.UL” ("Output safety value" [C.G08]) will be

forced to 0 if only one control output is configured and its value
is < 0.

D) The parameter “Fd.Fn” ("Out failure detection current

measurement" [C.I11]) will be forced to “nonE” if it is
assigned to a control output different from a time
proportional output.

E) The parameter “Fd.Ou” ("Out failure detection output

assignment" [C.I13]) will be forced to “nonE” if it is assigned
to an output configured as control output

F) The parameter “IP” ("Integral pre-load" [r.d05]) will be forced to

50.0 if only one control output is configured and its value

is < 0

mkc-ssi.pmd

06/07/2004, 12.19

41