17

4) Use copper conductors only.
5) Don’t run input wires together with power cables.
6) For 24 V DC the polarity is a not care condition.
7) The power supply input is fuse protected by a sub miniature fuse

rated T, 1A, 250 V.
When fuse is damaged, it is advisable to verify the power supply
circuit, so that it is necessary to send back the instrument to your
supplier.

8) The safety requirements for Permanently Connected

Equipment say:
- a switch or circuit-breaker shall be included in the building

installation;

- it shall be in close proximity to the equipment and within

easy reach of the operator;

- it shall be marked as the disconnecting device for the

equipment.

NOTE

NOTE

NOTE

NOTE

NOTE: a single switch or circuit-breaker can drive more than one
instrument.

9) When a neutral line is present please connect it to the 32 terminal.

G) POWER LINE WIRING

G) POWER LINE WIRING

G) POWER LINE WIRING

G) POWER LINE WIRING

G) POWER LINE WIRING

Fig. 18 POWER LINE WIRING
NOTES

NOTES

NOTES

NOTES

NOTES:
1) Before connecting the instrument to the power line, make sure

that line voltage corresponds to the description on the identifica-
tion label.

2) To avoid electrical shock, connect power line at the end of the

wiring procedure.

3) For supply connections use No 16 AWG or larger wires rated for

at least 75 °C.

33

L (L1)

Neutral

32

N (L2)

POWER LINE 100 V to

240 V A.C (50/60Hz)

or 24 V AC/DC

Line

mkc-ssi.pmd

06/07/2004, 12.19