Super Systems 20Q User Manual

Page 82

Advertising
background image

78

Gr.4Gr.4Gr.4Gr.4Gr.4

- Derivative time - [r.d04]

- Derivative time - [r.d04]

- Derivative time - [r.d04]

- Derivative time - [r.d04]

- Derivative time - [r.d04]

This parameter is available when at least one control output is
configured, “Cn.tP” [C.G02] is equal to “Pid” and "Pb" [r.d01] is
different from 0.
Range: From 00.00 to 10.00 mm.ss
NOTES

NOTES

NOTES

NOTES

NOTES:
1) When device is working with SMART algorithm and “Cn.tP”

[C.G02] is equal to “Pid”, the “td” value will be made equal to
a quarter of “ti” value.

2) When “Cn.tP” [C.G02] is equal to “Pi”, the derivative action is

excluded

- Integral preload - [r.d05]

- Integral preload - [r.d05]

- Integral preload - [r.d05]

- Integral preload - [r.d05]

- Integral preload - [r.d05]

This parameter is available when at least one control output is
configured and "Pb" [r.d01] is different from 0.
Ranges:
- from 0.0 to 100.0 % of the output when device is configured

with only one control output

- from -100.0 to 100.0 % of the output when device is

configured with two control outputs (split range excluded)

- Relative secondary output gain - [r.d06]

- Relative secondary output gain - [r.d06]

- Relative secondary output gain - [r.d06]

- Relative secondary output gain - [r.d06]

- Relative secondary output gain - [r.d06]

This parameter is available when two control outputs are
configured (split range excluded) and "Pb" [r.d01] is different from
0.
Range: from 0.20 to 2.00

- Overlap/dead band between main and

- Overlap/dead band between main and

- Overlap/dead band between main and

- Overlap/dead band between main and

- Overlap/dead band between main and

secondary outputs - [r.d07]

secondary outputs - [r.d07]

secondary outputs - [r.d07]

secondary outputs - [r.d07]

secondary outputs - [r.d07]

This parameter is available when two control outputs are
configured (split range excluded) and "Pb" [r.d01] is different from
0.
Range: from -20 to 50
NOTE

NOTE

NOTE

NOTE

NOTE: A negative value means a dead band while a positive
value means an overlap.