Super Systems 20Q User Manual

Page 16

Advertising
background image

12

+

_

_____

+

24

25

OUT 1

SOLID STATE

RELAY

+

_

_____

+

27

28

OUT 2

SOLID STATE

RELAY

Fig. 12 EXTERNAL SWITCH IN SERIES WITH THE INTERNAL

CONTACT

In this case it is recommended to install an additional RC
network across the external contact as show in Fig. 12
The value of capacitor (C) and resistor (R) are shown in the
following table.

Anyway the cable involved in relay output wiring must be as far
away as possible from input or communication cables.

E.2) VOLTAGE OUTPUTS FOR SSR DRIVE

E.2) VOLTAGE OUTPUTS FOR SSR DRIVE

E.2) VOLTAGE OUTPUTS FOR SSR DRIVE

E.2) VOLTAGE OUTPUTS FOR SSR DRIVE

E.2) VOLTAGE OUTPUTS FOR SSR DRIVE

Fig. 13 SSR DRIVE OUTPUT WIRING
Logic level 0

Logic level 0

Logic level 0

Logic level 0

Logic level 0: Vout < 0.5 V DC.
Logic level 1

Logic level 1

Logic level 1

Logic level 1

Logic level 1:
- 14 V + 20 % @ 20 mA
- 24 V + 20 % @ 1 mA.

Maximum current = 20 mA.

NOTE

NOTE

NOTE

NOTE

NOTE: This output is not isolated.
A double or reinforced insulation between instrument output and
power supply must be assured by the external solid state relay.

LOAD

(mA)

<40 mA
<150 mA
<0.5 A

C

(

µ

F)

0.047

0.1

0.33

R

(

)

100

22
47

P.

(W)

1/2

2
2

OPERATING

VOLTAGE

260 V AC
260 V AC
260 V AC

R

C

LOAD

LINE

mkc-ssi.pmd

06/07/2004, 12.19

12

Advertising