ProSoft Technology 5105-103M-PDPS User Manual

Page 107

Advertising
background image

5105-103M-PDPS ♦ ProLinx Gateway

Reference

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 107 of 144

November 24, 2010

TYPE 5: Identification

Bytes

Description

Spec

1

Value of 5

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

1

COL (compatibility level 2 or 3)

7.2.6.3

1

Char 1

7.2.6.2

1

Char 2

7.2.6.2

1

Char 3

7.2.6.2

1

Char 4

7.2.6.2

1

Char 5

7.2.6.2

1

Char 6

7.2.6.2

1

Char 7

7.2.6.2

1

Char 8

7.2.6.2

1

Manufacture byte

Free assignment

1

Manufacture byte

Free assignment

1

Manufacture byte

Free assignment

1

Manufacture byte

Free assignment

TYPE 6: Time synchronization

Bytes

Description

Spec

1

Value of 6

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

7

7-Octet binary time

7.2.6.29

TYPE 8: Termination of general interrogation

Bytes

Description

Spec

1

Value of 8

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

1

SCN (scan number 0 to 255)

7.2.6.21

Advertising