ProSoft Technology 5105-103M-PDPS User Manual

Page 121

Advertising
background image

5105-103M-PDPS ♦ ProLinx Gateway

Reference

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

User Manual

ProSoft Technology, Inc.

Page 121 of 144

November 24, 2010

Bit 0
Offline/Passive-idle
 0 = SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer

go offline.

 1= SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer

are started.

Bit 4, 5

 10 = Data Exchange State is Normal. The SPC3 has a correct configuration.

Module State: Word 10310 Byte 0
Indicates the current state of the module.
 0 = Normal Operation
 1 = Shutdown
 2 = File Transfer
 3 = SPC3 ASIC problem
 4 = Not in data exchange

Last Global Command: Word 10310 Byte 1
The value of the last global command code received from the master.

Bit

Designation

Significance

0

Reserved

1

Clear_Data

With this command the ASCI output data is deleted in data transfer

buffer and is changed to next transfer data buffer contents.

2

Unfreeze

With "Unfreeze": freezing input data is cancelled.

3

Freeze

The ASCI input data is fetched from next transfer buffer to data
transfer buffer and frozen. New input data is not fetched again until

the master sends the next "Freeze" command.

4

Unsync

The "Unsync" command cancels the "Sync" command.

5

Sync

The ASCI output data transferred with a WRITE_READ_DATA
telegram is changed from data transfer buffer next state buffer. The

following transferred output data is kept in data transfer buffer until

the next "Sync" command is given.

6,7

Reserved

The Reserved designation specifies that these bits are reserved for

future function expansions.

PROFIBUS Input Counter: 10311
Input counter is incremented each time the input data is updated.

PROFIBUS Output Counter: Word 10312
Output counter is incremented each time the output data is updated.

Words 10313 to 10399
No valid data