Diagnostics and Troubleshooting

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 86 of 144

ProSoft Technology, Inc.

November 24, 2010

2.15 Frequently Asked Questions

This section provides answers frequently asked questions about the ProLinx

103M module.

2.15.1 Why is the module not communicating with the slave?

First, ensure that the slave Data Link Address is configured as a slave (session)

in the configuration file. The module will only try to initialize slaves identified by

Data Link Addresses that are currently configured as sessions. Refer to technical

specification for your protection equipment for its Data Link Address. You should

also check to see if the common ASDU address is configured as a sector in the

module. Make sure all port communication parameters match the slave

parameters (baud rate, parity, and so on). Finally, look at the cables and ensure

that the correct communication mode is set (RS-232 or RS-495).

2.15.2 The slave is responding but I cannot see the monitor data in

the Module database.

Ensure that the monitor points are correctly configured. Refer to your protection

equipment’s documentation for the correct ASDU type, Function Code, and

Information Number. These values must match the parameters that are entered

for every monitor point in the [IEC-103 Master Session 0] section of the

configuration file.
The addressing type in the module database depends on the point ASDU type.

The Database Index parameter can be interpreted as bit, byte, word, or double-

word address. For more details, refer to Data Types and Mapping.

2.15.3 How can I confirm if the configuration was received by the

module?

You can verify this using the Debug menu. Refer to Diagnostics and

Troubleshooting in this manual for information on using the Debug menu.